Fire Pump Calculator

Churn · rated · 150% flow · pump curve reference

NFPA 20
Fire Pump Performance
Ad · 728×90 leaderboard

Common Fire Pump Sizes (Quick Select)


GPM
PSI

PSI

%
%

%
%

Enter rated flow and pressure to see results

Operating Point Flow (GPM) Net PSI Discharge PSI Est. BHP
Ad · 300×250

Common Fire Pump Sizes

Listed fire pump sizes per NFPA 20. Rated pressure varies by manufacturer and impeller selection. The pressures below are typical ranges — always verify from the specific pump curve.

Rated Flow (GPM) Typical Rated Pressure (PSI) Common Applications
Ad · responsive in-content

About This Fire Pump Calculator

This calculator provides a quick reference for estimating fire pump performance at three key operating points: churn (shutoff), rated flow, and 150% of rated flow. Enter the pump's rated flow and pressure, and the tool estimates the pump curve shape based on NFPA 20 performance requirements.

If suction pressure is known, the calculator also shows estimated discharge pressures at each operating point (suction + net pump pressure).

Common Uses

Limitations

This tool estimates a simplified pump curve using three points and a quadratic fit. Real pump curves are determined by manufacturer testing and depend on impeller size, speed, casing geometry, and other factors. Always use the certified pump curve from the manufacturer for design-level calculations, pump selection, and acceptance testing.

NFPA 20 Performance Requirements

NFPA 20 establishes minimum performance criteria for listed fire pumps at three operating points.

Churn (Shutoff / No Flow)

Churn pressure ≤ 140% of rated pressure
Pump must not exceed 140% of rated net pressure at zero flow.

Rated Point (100% Flow)

Pump delivers rated flow (GPM) at rated net pressure (PSI).
This is the pump's nameplate operating point.

150% of Rated Flow

Pressure at 150% flow ≥ 65% of rated pressure
Pump must maintain at least 65% of rated net pressure at 150% of rated flow.

Discharge Pressure

Discharge PSI = Suction PSI + Net Pump Pressure

Brake Horsepower (BHP)

BHP = (GPM × PSI) / (1714 × pump efficiency)

Where 1714 = constant converting GPM·PSI to horsepower
Efficiency is expressed as a decimal (e.g. 0.75 for 75%)

Water Horsepower (WHP)

WHP = (GPM × PSI) / 1714

WHP is the theoretical power delivered to the water.
BHP = WHP / efficiency (BHP is always greater than WHP).

Motor Sizing (Electric)

Required motor HP ≥ BHP at 150% flow × 1.15 service factor
Select the next standard motor size above this value.

Fire Pump Design Notes

Fire pumps are selected based on the system demand (flow and pressure) determined by hydraulic calculations. The pump must provide the required net pressure at the system demand flow rate, with suction pressure accounted for. Designers should evaluate the full pump curve — not just the rated point — to ensure adequate pressure across all expected operating conditions.

Key considerations beyond basic pump sizing include driver type (electric vs. diesel), controller requirements, test header sizing, suction supply adequacy (NPSH), jockey pump sizing, and alarm/supervisory signal integration. Fire pump installations are governed by NFPA 20 and must be reviewed by the authority having jurisdiction.

Professional-use disclaimer: This tool is provided for informational and educational reference only. It does not constitute engineering services, code compliance verification, design certification, professional engineering advice, or an engineer-client relationship. Users are responsible for independent verification and compliance with applicable codes, standards, laws, specifications, manufacturer data, and authority-having-jurisdiction requirements.

Frequently Asked Questions

What is churn pressure?

Churn (or shutoff) pressure is the pressure a fire pump produces at zero flow — when the discharge valve is closed. NFPA 20 limits churn to no more than 140% of the pump's rated pressure. High churn pressure is important for system relief valve sizing and component pressure ratings.

Why does NFPA 20 require performance at 150% flow?

The 150% flow point ensures the pump maintains usable pressure even when system demand exceeds the rated capacity. This can occur when more sprinklers operate than the design area assumed, or during hose stream demand. NFPA 20 requires at least 65% of rated pressure at 150% of rated flow.

What is net pump pressure vs. discharge pressure?

Net pump pressure is the pressure the pump adds to the water — the difference between discharge and suction pressure. Discharge pressure is the total pressure at the pump outlet: suction pressure plus net pump pressure. Hydraulic calculations use net pump pressure; field gauges read discharge and suction pressures directly.

How do I read a fire pump curve?

A pump curve plots net pressure (vertical axis) against flow rate (horizontal axis). The curve slopes downward from left to right — pressure decreases as flow increases. The three key points are churn (zero flow, maximum pressure), rated (100% flow at rated pressure), and the 150% point (150% flow at reduced pressure).

Can I use this for pump acceptance testing?

This calculator estimates a simplified curve. Actual acceptance testing per NFPA 25 requires field-measured data at churn, rated, and 150% flow using calibrated gauges and a flow meter. Compare field results to the manufacturer's certified curve, not to this estimate.

How is brake horsepower calculated?

BHP = (GPM × PSI) / (1714 × efficiency). Pump efficiency varies across the curve — it's highest near the rated point and drops at both churn and overload conditions. The 150% flow BHP is critical because NFPA 20 requires the driver (motor or engine) to be sized to handle this point without overloading.

Why is the 1.15 service factor applied to electric motors?

NFPA 20 requires electric motors for fire pumps to have a 1.15 service factor, meaning the motor can deliver 115% of its nameplate HP continuously. The motor must be sized so that the BHP at 150% flow, multiplied by the 1.15 SF, does not exceed the next standard motor size. Diesel engines do not use this service factor — they are rated directly at the 150% flow BHP.

Privacy Policy

Last updated:

This calculator runs in your browser. Values entered are not collected, stored, or transmitted. No account or login is required.

Advertising and analytics services may use cookies if enabled. Opt out at Google Ads Settings. We do not sell or share personal information. This site is not directed at children under 13.

Terms of Use

All tools and content are provided as-is for informational reference only. No warranty is made regarding accuracy, completeness, or fitness for a particular project. You are responsible for verifying all results independently.

Contact

For corrections, suggestions, or feedback: contact@yourdomain.com

Do not submit project-specific design requests or confidential information through this website.